Profibus IO module to ACS800 with protocol PPO5.
The object is created by the profibus configurator under a
ABB_ACS_Pb_Slave object in the node hierarchy. An
ABB_ACS800_PPO5 object is automatically generated that contains a
ABB_ACS800_PPO5_IoModule. See class ABB_ACS_Pb_Slave for more
information.
Connect the node object ABB_ACS800_PPO5_IoModule to an object
of class or subclass of ABB_ACS800_1 with the Connect IO method.
To adapt the frequency converter to this configuration, some settings
have to be performed, see class ABB_ACS_PPO5.
See also
Template Object |
I_ID.Description |
Parameter identification |
I_ID.ConversionOn |
1 |
I_ID.Representation |
2 |
I_IND.Description |
Array index |
I_IND.ConversionOn |
1 |
I_IND.Representation |
2 |
I_VALUE.Description |
Parameter value |
I_VALUE.ConversionOn |
1 |
I_VALUE.Representation |
1 |
I_SW.Description |
Status word from converter (fixed) |
I_SW.Identity |
9201 |
I_SW.ConversionOn |
1 |
I_SW.Representation |
3 |
I_ACT.Description |
Status word from converter (fixed) |
I_ACT.Identity |
1103 |
I_ACT.ConversionOn |
1 |
I_ACT.ScanInterval |
1 |
I_ACT.RawValRangeLow |
-2.000000e+04 |
I_ACT.RawValRangeHigh |
2.000000e+04 |
I_ACT.ChannelSigValRangeLow |
-2.000000e+04 |
I_ACT.ChannelSigValRangeHigh |
2.000000e+04 |
I_ACT.SensorPolyType |
1 |
I_ACT.SensorSigValRangeLow |
-2.000000e+04 |
I_ACT.SensorSigValRangeHigh |
2.000000e+04 |
I_ACT.ActValRangeLow |
-1.500000e+03 |
I_ACT.ActValRangeHigh |
1.500000e+03 |
I_ACT.Representation |
2 |
I_PZD3.Description |
Status word from converter |
I_PZD3.Identity |
5106 |
I_PZD3.ConversionOn |
1 |
I_PZD3.RawValRangeLow |
-1.000000e+04 |
I_PZD3.RawValRangeHigh |
1.000000e+04 |
I_PZD3.ChannelSigValRangeLow |
-1.000000e+04 |
I_PZD3.ChannelSigValRangeHigh |
1.000000e+04 |
I_PZD3.SensorPolyType |
1 |
I_PZD3.SensorSigValRangeLow |
-1.000000e+04 |
I_PZD3.SensorSigValRangeHigh |
1.000000e+04 |
I_PZD3.ActValRangeLow |
-1.000000e+03 |
I_PZD3.ActValRangeHigh |
1.000000e+03 |
I_PZD3.Representation |
2 |
I_PZD4.Description |
Status word from converter |
I_PZD4.Identity |
5108 |
I_PZD4.ConversionOn |
1 |
I_PZD4.RawValRangeLow |
-3.276800e+04 |
I_PZD4.RawValRangeHigh |
3.276700e+04 |
I_PZD4.ChannelSigValRangeLow |
-3.276800e+04 |
I_PZD4.ChannelSigValRangeHigh |
3.276700e+04 |
I_PZD4.SensorPolyType |
1 |
I_PZD4.SensorSigValRangeLow |
-3.276800e+04 |
I_PZD4.SensorSigValRangeHigh |
3.276700e+04 |
I_PZD4.ActValRangeLow |
-3.276800e+02 |
I_PZD4.ActValRangeHigh |
3.276700e+02 |
I_PZD4.Representation |
2 |
I_PZD5.Description |
Status bits from converter |
I_PZD5.Identity |
5110 |
I_PZD5.ConversionOn |
1 |
I_PZD5.Representation |
3 |
I_PZD6.Description |
Status bits from converter |
I_PZD6.Identity |
5112 |
I_PZD6.ConversionOn |
1 |
I_PZD6.Representation |
3 |
I_PZD7.Description |
Status bits from converter |
I_PZD7.Identity |
5114 |
I_PZD7.ConversionOn |
1 |
I_PZD7.Representation |
3 |
I_PZD8.Description |
Status bits from converter |
I_PZD8.Identity |
5116 |
I_PZD8.ConversionOn |
1 |
I_PZD8.Representation |
3 |
I_PZD9.Description |
Status bits from converter |
I_PZD9.Identity |
5118 |
I_PZD9.ConversionOn |
1 |
I_PZD9.Representation |
3 |
I_PZD10.Description |
Status bits from converter |
I_PZD10.Identity |
5120 |
I_PZD10.ConversionOn |
1 |
I_PZD10.Representation |
3 |
O_ID.Description |
Parameter identification |
O_ID.Representation |
3 |
O_IND.Description |
Array index |
O_IND.Representation |
3 |
O_VALUE.Description |
Parameter value |
O_VALUE.Representation |
1 |
O_CW.Description |
Control word to converter (fixed) |
O_CW.Identity |
9004 |
O_CW.Representation |
3 |
O_REF.Description |
Referencevalue word to converter (fixed) |
O_REF.Identity |
9004 |
O_REF.OutPolyType |
1 |
O_REF.ActValRangeLow |
-1.500000e+03 |
O_REF.ActValRangeHigh |
1.500000e+03 |
O_REF.SensorSigValRangeLow |
-2.000000e+04 |
O_REF.SensorSigValRangeHigh |
2.000000e+04 |
O_REF.ChannelSigValRangeLow |
-2.000000e+04 |
O_REF.ChannelSigValRangeHigh |
2.000000e+04 |
O_REF.RawValRangeLow |
-2.000000e+04 |
O_REF.RawValRangeHigh |
2.000000e+04 |
O_REF.Representation |
2 |
O_PZD3.Description |
Referencevalue word to converter |
O_PZD3.Identity |
5105 |
O_PZD3.OutPolyType |
1 |
O_PZD3.ActValRangeHigh |
6.000000e+02 |
O_PZD3.SensorSigValRangeHigh |
6.000000e+04 |
O_PZD3.ChannelSigValRangeHigh |
6.000000e+04 |
O_PZD3.RawValRangeHigh |
6.000000e+04 |
O_PZD3.Representation |
2 |
O_PZD4.Description |
Referencevalue word to converter |
O_PZD4.Identity |
5107 |
O_PZD4.OutPolyType |
1 |
O_PZD4.ActValRangeHigh |
6.000000e+02 |
O_PZD4.SensorSigValRangeHigh |
6.000000e+04 |
O_PZD4.ChannelSigValRangeHigh |
6.000000e+04 |
O_PZD4.RawValRangeHigh |
6.000000e+04 |
O_PZD4.Representation |
2 |
O_PZD5.Description |
Referencevalue word to converter |
O_PZD5.Identity |
5109 |
O_PZD5.OutPolyType |
1 |
O_PZD5.ActValRangeLow |
-3.276800e+04 |
O_PZD5.ActValRangeHigh |
3.276700e+04 |
O_PZD5.SensorSigValRangeLow |
-3.276800e+04 |
O_PZD5.SensorSigValRangeHigh |
3.276700e+04 |
O_PZD5.ChannelSigValRangeLow |
-3.276800e+04 |
O_PZD5.ChannelSigValRangeHigh |
3.276700e+04 |
O_PZD5.RawValRangeLow |
-3.276800e+04 |
O_PZD5.RawValRangeHigh |
3.276700e+04 |
O_PZD5.Representation |
2 |
O_PZD6.Description |
Referencevalue word to converter |
O_PZD6.Identity |
5111 |
O_PZD6.Representation |
2 |
O_PZD7.Description |
Referencevalue word to converter |
O_PZD7.Identity |
5113 |
O_PZD7.Representation |
2 |
O_PZD8.Description |
Referencevalue word to converter |
O_PZD8.Identity |
5115 |
O_PZD8.Representation |
2 |
O_PZD9.Description |
Referencevalue word to converter |
O_PZD9.Identity |
5117 |
O_PZD9.Representation |
2 |
O_PZD10.Description |
Referencevalue word to converter |
O_PZD10.Identity |
5119 |
O_PZD10.Representation |
2 |